range | EasyPact |
---|---|
product name | EasyPact TVS |
product or component type | Contactor |
device short name | LC1E |
contactor application | Motor control Resistive load |
utilisation category | AC-1 AC-3 |
poles description | 3P |
power pole contact composition | 3 NO |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 50 A (at <55 °C) at <= 440 V AC AC-1 for power circuit 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit |
motor power kW | 18.5 kW at 500 V AC 50/60 Hz (AC-3) 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) 9 kW at 220...230 V AC 50/60 Hz (AC-3) 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) 18.5 kW at 415 V AC 50/60 Hz (AC-3) 18.5 kW at 440 V AC 50/60 Hz (AC-3) |
control circuit type | AC at 50 Hz |
[Uc] control circuit voltage | 24 V AC 50 Hz |
height | 84 mm |
width | 56 mm |
depth | 86 mm |
net weight | 0.45 kg |
colour | Grey (RAL 7011) |
auxiliary contact composition | 1 NO |
---|---|
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
overvoltage category | III |
Irms rated making capacity | 380 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
rated breaking capacity | 304 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 60 A 40 °C - 600 s for power circuit 310 A 40 °C - 10 s for power circuit 150 A 40 °C - 60 s for power circuit |
associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit |
average impedance | 2.5 mOhm - Ith 50 A 50 Hz for power circuit |
power dissipation per pole | 2.9 W AC-3 5 W AC-1 |
control circuit voltage limits | Operational: 0.85...1.1 Uc at 50 Hz (at <55 °C) Drop-out: 0.3...0.6 Uc at 50 Hz (at <55 °C) |
operating time | 12...22 ms on closing 4...19 ms on opening |
mechanical durability | 8000000 cycles |
maximum operating rate | 1800 cyc/h 60 °C |
inrush power in VA | 95 VA 50 Hz cos phi 0.75 (at 20 °C) 95 VA 60 Hz cos phi 0.75 (at 20 °C) |
hold-in power consumption in VA | 8.3 VA 50 Hz cos phi 0.3 (at 20 °C) 8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
heat dissipation | 2…3 W for control circuit |
minimum switching current | 5 mA for control circuit |
minimum switching voltage | 17 V for control circuit |
non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact |
insulation resistance | > 10 MOhm for control circuit |
electrical durability | 350000 cycles AC-1 900000 cycles AC-3 |
mounting support | DIN rail Plate |
connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end |
Recommended tightening torque | Control circuit: 1.2 N.m Power circuit: 2.1 N.m |
Max tightening torque | Control circuit: 1.4 N.m Power circuit: 2.3 N.m |
standards | IEC 60947-4-1 IEC 60947-5-1 IEC 60947-1 |
---|---|
product certifications | EAC CE |
IP degree of protection | IP2x conforming to IEC 60529 |
protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 test Db |
pollution degree | 3 |
ambient air temperature for operation | -5…55 °C |
ambient air temperature for storage | -60…80 °C |
permissible ambient air temperature around the device | -20…70 °C at Uc |
operating altitude | 3000 m without derating |
fire resistance | 850 °C conforming to IEC 60695-2-1 |
mechanical robustness | Vibrations contactor open: 1.5 Gn, 5...300 Hz Vibrations contactor closed: 3 Gn, 5...300 Hz Shocks contactor closed: 10 Gn for 11 ms Shocks contactor open: 6 Gn for 11 ms |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 456 g |
Package 1 Height | 9.2 cm |
Package 1 width | 5.8 cm |
Package 1 Length | 8.5 cm |
Sustainable offer status | Green Premium product |
---|---|
REACh Regulation | REACh Declaration |
REACh free of SVHC | Yes |
EU RoHS Directive | Compliant EU RoHS Declaration |
Toxic heavy metal free | Yes |
Mercury free | Yes |
RoHS exemption information | Yes |
China RoHS Regulation | China RoHS declaration |
Environmental Disclosure | Product Environmental Profile |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Warranty | 18 months |
---|